Mycobacterium terrae

Bohrerova & Linden 2006 · 254 nm

Mycobacterium Water 254 nm

Test conditions & context

Type Mycobacterium
Medium Water
Test wavelength 254 nm
Particle size 3000 nm
Author Bohrerova & Linden
Year 2006

UV-C dose–response (D-values)

A D-value is the UV-C dose (in mJ/cm²) needed for a given log-reduction. D90 = 90 % inactivation = 1-log; D99 = 99 % = 2-log; D99.9 = 99.9 % = 3-log, and so on. Values come from the cited study under its specific test conditions.

Reduction log Dose (mJ/cm²)
D90 90 % 1-log 3.9 mJ/cm²
D99 99 % 2-log 9.3 mJ/cm²
D99.9 99.9 % 3-log 16 mJ/cm²

Morphology & UV-C resistance

Waxy, mycolic-acid-rich cell wall → slightly elevated UV-C resistance; additionally shielded in hot-water-system biofilms.

Primary source

Bohrerova & Linden (2006). iuva.org/resources/Resource%20Documents/Malayeri-Fluence%20Required%20to%20Achieve%20Incremental%20Log%20Inactivation%20of%20Bacteria%2C%20Protozoa%2C%20Viruses%20and%20Algae.pdf